Home > WT - PACKAGE WATER TREATMENT PLANTS

TYPICAL DIAGRAM PROCESS

 


 
 Characteristics

Model
SR300
SR550
SR1000
SR1500
SR2200
SR3000
SR4500
SR6000
Q average flow (m3/ h)
3
5,5
10
15
22,5
30
45
60
Q maximum flow(m3/h)
3,6
6,7
12,5
18
27
36
55
72
Connection
1 ¼”
1 ½”
2”
2 ½”
3”
3”
4”
5”
Washing connection
2 ½”
3”
4”
5”
6”
2 x 6”
2 x 6”
2 x 8”
Washing flow (en m3/h)
3,25
7
10,5
15
23
19 x 2
25 x2
35x2
Max. tank height (m)
20
20
20
20
20
20
20
20
Minimum tank volume (m3)
5
9
14
18
26
25
35
45
Approximate length (mm)
1700
2500
4700
5300
6000
2x 4300
2x6000
2x6000
Approximate width (mm
1700
1700
1700
2200
2300
2x2300
2x2300
2x3300
Approximate height (mm
2300
2300
2300
2300
2400
2400
2400
2400
Hypochlorite tank(liters)
30
50
75
100
130
230
230
500
Dosing
Hydraulic
Pump
Pump
Pump
Pump
Pump
Pump
Pump
Aluminum Sulphate tank (liters)
1308
230
350
500
500
1000
1000
1000
Dosing
Pump
Pump
Pump
Pump
Pump
Pump
Pump
Pump
Polyelectrolite tank (liters)
75
130
130
230
230
500
500
500
Dosing
Option
Pump
Pump
Pump
Pump
Pump
Pump
Pump
Mixers (hp)
½
½
¾
1
1
1
1
1
Daily performance (22hs) in m3
65
120
250
330
450
660
100
1350
Number of inhabitants (aproxímate)
320
680
1200
1600
2200
400
5000
6700
Note:  These are average values.  Final measures will be depending on design parameters.




Home - Contact Us

WWTP: Pretreatment - Biological Treatment - Sludge Treatment - Package Treatment Plants
WT: Reverse Osmosis Systems - Water Softners - Filtration - Ultrafiltration - UV Equipments - Ozone Generators - Package Treatment Plants

Versión Español

6110 NW, 32nd Terrace - Fort Lauderdale - Fl33309 - USA
phone/fax: 1 954 917 4081

Copyright © 2003 PWP Pure Water Process. All rights reserved.